Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
De complete datasheet als PDF downloaden:
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.8 W | |
Power consumption | 0.8 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 |
|
RTD or resistance | type Pt100 (EN 60751: 1995) type Ni100 (DIN 43760) 0 ... 500 Ω (including lead resistance) |
|
Measuring current | approx. 400 µA with RTD | |
Lead resistance | max. 50 Ω per line | |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) |
|
Voltage | 0 ... 10 V , 2 ... 10 V | |
Current | 0 ... 20 mA , 4 ... 20 mA | |
Load | 20 Ω for 20 mA; 200 kΩ for 10 V | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9; output II: terminals 10, 11, 12 | |
Output I, II | relay | |
Contact loading | 253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load | |
Mechanical life | 2 x 107 switching cycles | |
Transfer characteristics | ||
Resolution | temperature: 0.0625 °C, resistance: 62.5 mΩ, voltage: 62.5 µV, current: 625 nA | |
Deviation | ||
Voltage input | ± 0.02 % of 10 V measuring range | |
Resistance input | ± 0.025 % of measuring range (4-wire connection) | |
Current input | ± 0.02 % of 20 mA measuring range | |
Pt100 | ± 0.01 % of abs. temperature value of switching point in K + 0.2 K (4-wire connection) | |
Thermocouple | ± 0.05 % of abs. temperature value of switching point in K + 1.1 K (1.2 K for thermocouple types R and S) this includes ± 0.8 K fault of the cold junction compensation (CJC) (+0.9 K for thermocouple types R and S). Note! Because the sensitivity of thermocouples is, in general, lower at low temperatures than at high temperatures, the specified accuracy figures cannot be guaranteed when measuring temperatures below those listed here. -50 °C (type E and K thermocouples) -100 °C (type J, L and T thermocouples) +500 °C (type B thermocouple) |
|
Influence of ambient temperature | ||
Pt100 | ± (0.0015 % of abs. temperature value of switching point in K + 0.01 K)/K ΔTamb*) | |
Thermocouple | ± (0.004 % of abs. temperature value of switching point in K + 0.01 K) / KΔTamb*) | |
Voltage input | ± (0.007 % of the switching point voltage) / KΔTamb*) | |
Current input | ± (0.004 % of the switching point current)/KΔTamb*) *) ΔTamb = ambient temperature change referenced to 23 °C (296 K) |
|
Influence of supply voltage | < 0.001 % of sensor input range | |
Input delay | ≤ 370 ms (rise time and energizing delay of relay) | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output I/II | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Power supply/programming input | no electrical isolation | |
Indicators/settings | ||
Display elements | LEDs | |
Configuration | via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Height | 119 mm | |
Width | 20 mm | |
Length | 115 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210122 |
ECLASS 12.0 | 27210122 |
ECLASS 11.0 | 27210122 |
ECLASS 10.0.1 | 27210122 |
ECLASS 9.0 | 27210122 |
ECLASS 8.0 | 27210122 |
ECLASS 5.1 | 27210122 |
ETIM 9.0 | EC002654 |
ETIM 8.0 | EC002654 |
ETIM 7.0 | EC002654 |
ETIM 6.0 | EC002654 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
Safety and Security Documentation | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
Handleiding | HOL | 56 KB | |
Manuals | |||
Manual KFD2-GU-(Ex)1 | ENG | 1294 KB | |
System Manual | ENG | 3694 KB | |
Installation and configuration guide Device Type Manager (DTM) | ENG | 8665 KB |
CAD | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2510 KB |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
EPLAN macro EDZ / EPLAN Makro EDZ | ALL | EDZ | 62 KB |
Declaration of Conformity | Certificaatnummer | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|---|
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0087A | ALL | 311 KB |
Frameworks | Vrijgave-informatie | Bestandstype | Bestandsgrootte |
---|---|---|---|
PACTware 4.1 SP6 / PACTware 4.1 SP6 | 4.1.0.53 | ZIP | 43327 KB |
PACTware 5.0 / PACTware 5.0 | 5.0.5.31 | ZIP | 44203 KB |
Device Description Files/Drivers | |||
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 2 | 1.4.110.76 | ZIP | 32633 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|